Power Factor controller
Current Position :Home » Products » Low » Power Factor controller
Detail

●  The Computer SDARE-12L PF regulators measure cosφ in supply system and control the connection and disconnection of capacitors to obtain a target programmed value.


●  The manual is an easy guide for the use and operation of the Computer SDARE-12L.For manual can be downloaded form the web site of Circutor:www.sdare.net


Display
1 Standard mode: Displays cosφ
2 cosφ lndication/setting
3 C/K setting. See paragraph 6
4 Program setting.See 4.2
5 Delay time setting for switching on/off operations
6 Nr of steps setting
7 Setting CT phase and polarity connection
8
-Cursor keys (when in setting mode)
-Manual ON /OF (push during more that 1s when in RUN mode)
-Push both to see the Nr of connected steps
9 SETUP KEY:Push during more that 1s to enter SETUP mode
10 Lagging current indication (inductive load)
11 Leading current indication (Capacitive load )


图片1.jpg Any manipulation or use of the equipment out of the conditions specified by the manufacturer may put in risk the user safety. Before any maintenance operation the equipment must be disconnected from power supply. In case of miss operation fault the equipment must be disconnected from supply and remain out of service ensuring against any accidental reconnection.


1.Regulator Connection

For proper operation it`s necessary to install a current transformer, CT(normally ln /5 A), which primary must be sized according to the maximum expected load current in the installation.

The regulator supply (C-D terminals) must be taken between two phases and the CT should be located in the third phase. See technical characteristics for cable sizes and required protections.


The current transformer, CT, must be located so that it measures the whole load current plus the correction capacitors.


2.TECHNICAL CHARACTERISTICS

Supply and V measurement input terminals(C-D) 400 VAC +15%-10%; 45-65 Hz, Connect preferably to phases L2-L3
Supply cables size and protection Cross section 1.52 ; 0 , 5 to 2A Fuses gl type
Current measurement circuit Current transformer (CT), In /5. Place preferably in phase L1 Minimum cabling cross section 2.5mm2
Current measurement margin 0.1to 5 A (maximum overload+20%)
Accuracy of measurements Voltage and current :1%; cosφ :2%±1 digit
Default cosφ setting 1
Power consumption 6 VA (no load);7.5 VA (6 relays connected); 9.5 VA (12 relays connected)
Display 1 line ×3 digits ×7segments +20 icons
Output Relay Contacts Max .250 VAC,10 A,AC1
Output Relay Cabling and Protection Cabling cross section 1.5mm2.Protection by means of a 6A circuit breaker (C curve) or by a 6A fuse (gi type)
Safety / insulation Last relay automatically set as alarm output , if not in use
Compliant to the following Standards EN 61010,EN 61000-3-2,EN 61000-3-3,EN 50081-2,EN50082-1,EN 50082-2,EN 61000-4-2,EN 61000-4-4,EN 61000-4-8,EN61000-4-5,EN 61000-4-11,UL94
Safety / insulation Category 111,Class 11,According to EN 61010-1
Environment Limit conditions Temperature limits : -20℃ a +60℃; Relative Humidity 95% (without condensation).Max Altitude :2000m
Protection degree
IP51 (panel mounted)
IP30(regulator box), According to EN-60529
Control system FCP (Minimum number of operations)


3.Four Quadradrants Operation

The computer SDRK-12L regulators operate in 4 quadrants (suitable for imported or exported active power ). For exported power ,a negative symbol is displayed in the cosφ indication. Check phase connection and setup if there is no exported energy and the indication is not correct (see 4.3,SET-UP-phase)